1 September 2025
GB300 pod setup (hypothetical, hardware agnostic) – Total TDP ≈ 2.42mW / Max power ≈ 2.78mW
Here’s a max‑GB300, 18‑rack airtime network that preserves a proper leaf–spine fabric, shared storage, and OOB/timing, while squeezing in the most GB300 GPUs possible.
- Total racks: 18
- GB300 accelerator racks: 16 (R3–R18)
- Support racks:
- R1 = Fabric + Edge + OOB + Timing (collapsed into one rack)
- R2 = Shared Storage (Ceph + NVMe‑oF)
- Accelerator density: 8× 4U servers per GB300 rack, each with 8× GB300 → 64 GB300/rack
- Total GB300 GPUs: 16 × 64 = 1,024
Fabric & overlay (brief)
- Leaf/ToR: Dual PTP‑aware 400 GbE ToRs per rack (MLAG/vPC), plus 1× OOB switch.
- Spine: 4× 64×400 GbE non‑blocking (in R1).
- Overlay: EVPN‑VXLAN over iBGP underlay (ECMP).
- Timing: GNSS‑backed PTP grandmasters (R1) → boundary clocks (R1) → PTP‑aware ToRs → NIC HW timestamp on DUs/AI servers.
- Storage: NVMe‑oF over RoCE; Ceph for block/object.
Power breakdown (assumptions shown)
Relevant assumptions:
- GB300 accelerator rack (R3–R18): 150 kW DC typical per rack (includes servers + ToRs + OOB).
- Max draw estimate: 1.15× typical (common industry planning factor).
- PSU+distribution efficiency for AC @ wall: 92%.
- Recommended breaker headroom: +10%.
Per‑rack power (DC → AC → breaker)
- GB300 rack (each R3–R18):
- DC typical: 150.0 kW → AC typical: 163.0 kW → Breaker: 179.3 kW
- DC max est.: 172.5 kW → AC max: 187.5 kW → Breaker: 206.3 kW
- R1 (Fabric + Edge + OOB + Timing): (itemized typical DC)
- 4× spines ≈ 4.0 kW, 2× edge routers ≈ 4.0 kW,
2× PTP BC ≈ 0.16 kW, RR 0.15 kW, L4/L7 0.30 kW,
packet broker 0.30 kW, netmgmt agg 0.15 kW,
2× OOB cores 0.30 kW, 2× consoles 0.14 kW,
2× PTP GMs 0.18 kW, GNSS 0.03 kW, NTP 0.05 kW, KVM 0.06 kW - DC typical: 9.8 kW → AC typical: 10.7 kW → Breaker: 11.8 kW
- DC max est.: 11.3 kW → AC max: 12.3 kW → Breaker: 13.5 kW
- 4× spines ≈ 4.0 kW, 2× edge routers ≈ 4.0 kW,
- R2 (Storage): (typical DC)
- 3× Ceph nodes 2.1 kW, 2× NVMe‑oF targets 1.4 kW, 2× JBOD 1.2 kW,
2× ToR 1.8 kW, OOB 0.10 kW - DC typical: 6.6 kW → AC typical: 7.2 kW → Breaker: 7.9 kW
- DC max est.: 7.6 kW → AC max: 8.3 kW → Breaker: 9.1 kW
- 3× Ceph nodes 2.1 kW, 2× NVMe‑oF targets 1.4 kW, 2× JBOD 1.2 kW,
Site totals (all 18 racks)
- DC typical: 2,416.4 kW
- (16× GB300 racks = 2,400.0 kW + R1 9.8 kW + R2 6.6 kW)
- DC max (est.): 2,778.9 kW
- (16× 172.5 kW + R1 11.3 kW + R2 7.6 kW)
- AC @ wall (92% eff):
- Typical: 2,626.5 kW
- Max (est.): 3,020.5 kW
- Recommended breaker capacity (+10%):
- Typical: 2,889.2 kW
- Max (est.): 3,322.6 kW